Home Contact Us Sitemap
About Us Products Quality Downloads /Utilities Careers News Enquiry
 
    Flow Instruments
 
Select Products  
 
    Flow Indicator Totaliser
 

Nippon Nippoflow Indiacator Totaliser

Linear or Square Root Operation Possible.

  • 96H x 96W x 150D inmm
  • 4-20 mA, or Volt Pulses Input
  • 8 Digits Totalising
  • 4 Digits Flow Rate Indicator

"NIPPO FLOW" series is designed with help of State-of-art micro controllers. The instruments can measure Flow accurately, it accepts signals, from FLOW TRANSMITTERS and calculates flow rate and also integrates the same. The 4 digit indicator displays the instantaneous flow rate and 10 digit counter displays TOTAL FLOW.

Specifications:  
 
INPUTS 4-20 mA, or Volt Pulses.
RANGE Flow Totaliser - 10 digits.
Flow Rate - 0-9999 Units (Lit/Min or Kg/Hr or Tons/Hr or M3/Hr)
ACCURACY Cent Percent
DISPLAY 10 digits bright seven segment display for Flow Totaliser.
4 digits bright seven segment display for Flow Rate
PARAMETER SETTING By soft touch, Elegant, Sturdy & user friendly membrane key pads.
MEMORY 10 years NVRAM.
COMPUTER INTERFACE RS232 or RS 485, MODBUS available.
SUPPLY 90-260 VAC, 50 Hz, SMPS
AMBIENT CONDITION Temp 55°C & Relative Humidity 99%
RETRANSMISSION Available
• 4-20 mA for Flow rate.
• Pulses for Flow Counts.
SET POINTS 2 Nos, Possible for Flow rate & Flow Totaliser.
OUTPUT 2 Relays, rated 230 V / 6 Amp.
BOX 96(H) X 192(W) X 180(D) Din Size box with modular design.
Also available in FLAMEPROOF ENCLOSURES
For Hazardous application.
 
 
Differential Pressure Measurement for Flow rates : Generally this method is used for measuring flow of gas, steam and liquids of low viscosity. An obstruction in the pipeline is generated by an element (orifice plate) creates pressure difference before and after the element. This differential pressure (pressure low) is proportional to square of the flow rate.
 
Electro- magnetic flow measurement : This method is used in application where liquid is electrically conductive. E.g. water, acids, alkalis, milk, beer, pulp slurry etc. Faraday's law of induction is the principle used. Electromagnetic Force (E.M.F) is induced when conductive material passes through a magnetic field. The flowing medium is conductor and induced voltage is proportional to flow velocity.
 
copyright by 2006-2007 NIPPON INSTRUMENTS (INDIA) Pvt. LTD
Website managed by Web-Mantra.com